Why does refrigeration fail more often over summer and Christmas?
Refrigeration fails more often in summer because heat and trading volume peak at the same time. A system has to push the heat it removes out into the surrounding air, and the hotter that air is, the harder every component works. Add doors opening constantly, extra deliveries and cool rooms packed to the ceiling, and a small weakness that went unnoticed in August becomes a breakdown in the week before Christmas. In Canterbury, breakdown calls climb sharply from December and stay high through the warm months.
The ten checks below are ordered so the first eight can be started by your own staff, and the last two are planning decisions for the owner or manager.
What should be on a pre-Christmas refrigeration checklist?
A pre-Christmas checklist should cover heat rejection, air sealing, drainage, monitoring and capacity, in that order.
| Check | Who does it |
|---|---|
| 1. Condenser coils clean | Staff look; engineer cleans |
| 2. Airflow clear around units | Staff |
| 3. Door seals and hinges | Staff check; engineer replaces |
| 4. Evaporators and drains | Staff look; engineer clears and repairs |
| 5. Temperature logging | Staff |
| 6. Alarms tested | Staff, with engineer support |
| 7. Ice machines cleaned | Staff or engineer |
| 8. Refrigerant leak signs | Staff look; certified technician tests and repairs |
| 9. Capacity planned for extra stock | Manager |
| 10. Service booked, after-hours process known | Manager |
1. Are the condenser coils clean?
A dirty condenser is the single most common cause of hot-weather breakdowns. The condenser is the finned coil on the outdoor unit, or behind the grille on a self-contained cabinet. If you can see a mat of dust, grease, lint or leaves, the system is already running hotter than it should. Coil fins are soft and easily flattened, so have cleaning done properly rather than attacking it with a stiff brush or a water blaster.
2. Is the airflow clear around every unit?
Every unit needs free air in and out. Move cartons, crates and rubbish bins away from outdoor units and plant rooms, and keep the vents on cabinets and under-bench fridges unobstructed. Inside cool rooms, keep stock away from the evaporator fans and off the walls so cold air can circulate around the load.
3. Are the door seals and hinges in good order?
A door that does not seal lets in warm, moist air all day. Look for torn, hardened or flattened seals and doors that have dropped on their hinges or no longer self-close. Close the door on a strip of paper: if it slides out easily, the seal is not doing its job. Check strip curtains are complete, and on freezers look for ice around the frame, which suggests a door heater has failed.
4. Are the evaporators and drains clear?
The evaporator coil inside the room or cabinet should be free of heavy ice. Light frost between defrosts is normal; a solid block of ice is not, and it points to a defrost fault or an air leak. Check drip trays and drain lines are running freely, because a blocked drain turns into water on the floor or ice growing into the coil. Do not chip ice off a coil.
5. Is temperature logging working and accurate?
Your records are only useful if the readings are right. Compare each display against a separate thermometer you trust, and confirm chilled storage is holding 5°C or below and frozen storage is holding -18°C or colder. Check that manual log sheets are being filled in, or that your automatic logger is recording and somebody is looking at it.
6. Have the alarms been tested?
An alarm that nobody receives is no protection. Test the high-temperature alarm on each room, and confirm that any text or phone alerts go to people who will be available over the holiday period, not to someone on leave or a number that has changed.
7. Have the ice machines been cleaned?
Ice machines work hardest in summer and are the equipment most often overlooked. Clean and sanitise the machine and bin following the manufacturer's instructions, change the water filter if one is fitted, and clean the air filter or condenser. Slow production, small or cloudy ice and an off taste are all signs it is overdue.
8. Are there any signs of a refrigerant leak?
A slow leak that the system coped with in winter will stop it keeping up in a heatwave. Warning signs are oily patches on pipe joints or under the unit, a system that runs almost continuously, a gradual loss of temperature, or frost on only part of the evaporator. Leak testing and repair must be done by a certified refrigeration technician.
9. Do you have enough capacity for Christmas stock?
Overloading is a fault you can plan your way out of. A cool room is built to hold product cold, not to pull down a mountain of warm stock, and packing it to the ceiling blocks the airflow it depends on. Stagger deliveries where you can, and if the numbers do not add up, arrange extra space. Our hire and leasing service includes chiller trailer hire for exactly this, and it is worth arranging early.
10. Is a service booked, and does everyone know the after-hours process?
A pre-summer service catches the faults staff cannot see, such as worn contactors, weak fan motors, low refrigerant charge and incorrect defrost settings, while there is still time to get parts. Book refrigeration maintenance before the rush. Then make sure every shift, including casual and holiday staff, knows what to do if something fails at night: where the number is, who can approve a call-out, and where stock can be moved. Our 24/7 refrigeration breakdowns page has the details.
Put the breakdown number where night staff will see it. Write 03 384 3374 on the cool room door and by the switchboard. It is answered 24/7, including weekends and public holidays.
When should I book a pre-summer service?
Book it now, in November, rather than waiting for the first hot week. Engineers' diaries fill as temperatures rise, and a repair found early in the month can be finished before your busiest trading days instead of during them.
To book a pre-Christmas service, call Southfreeze on 03 384 3374 or see refrigeration maintenance. If something has already failed, the same number is answered 24/7.